Conduit Fill Calculator (NEC Chapter 9)
How many THHN conductors fit in EMT conduit under the NEC Chapter 9 fill limits - 53% for one wire, 31% for two, 40% for three or more - with the resulting fill percentage.
Pick the conduit and wire, and enter the conductor count.
How it works
Total wire area = conductor count × the NEC Chapter 9 Table 5 area per conductor. The allowed area is the conduit bore (Table 4, EMT) × the fill limit: 53% for one conductor, 31% for two, 40% for three or more.
- Example: three 12 AWG THHN in 1/2 in EMT fill 13.3% - comfortably legal; ten of them hit 44% and fail.
- Mixed sizes: compute each type's area and add them; this tool checks one size at a time.
- Ground wires count as conductors for fill; jamming (3+ wires wedged) and bending space are separate rules.
Tables are for EMT with THHN/THWN. PVC, IMC and rigid steel have slightly different bores, and other insulations (XHHW, THW) are larger - check NEC Chapter 9 Tables 4 and 5 for the exact combination.