Harmonic Distortion (THD) Calculator
Total harmonic distortion of current or voltage from the fundamental and the harmonic components, plus the true RMS including harmonics.
Enter the fundamental and any harmonic components present; leave the rest at 0. Each field accepts amps or % of fundamental.
How it works
Total harmonic distortion compares the harmonic content with the fundamental:
THD = √(I₂² + I₃² + I₄² + …) / I₁ × 100%, and Iᵡₗₛ = √(I₁² + I₂² + …) = I₁√(1 + THD²).
Enter harmonic values in amps. Leave absent harmonics at 0.
Worked example
I₁ = 100 A, I₅ = 20 A, I₇ = 11 A, others 0. THD = √(400+121)/100 = 22.8%. True RMS = 100 × √(1+0.0520) = 102.56 A.
Assumptions and limitations
- THD referenced to the fundamental (IEC practice), not to the total RMS.
- Interharmonics and phase angles are not included; THD is a magnitude measure.
- Typical limits: IEEE 519 sets current THD limits at the point of common coupling by system short-circuit ratio.