Heat Exchanger Effectiveness-NTU Calculator


Effectiveness-NTU sizing of a heat exchanger: capacity rates, overall U and area give NTU and effectiveness, hence the duty and both outlet temperatures.

Capacity rate = mass flow × specific heat. Effectiveness relations for counterflow, parallel flow and 1-2 shell-and-tube.

Enter your values:
Results:

How it works

With capacity rates Cₕ = (m·cₚ)ₕ and C₊ = (m·cₚ)₊, Cₗᵢₙ the smaller and Cᵣ = Cₗᵢₙ/Cₗₐₓ:

NTU = UA/Cₗᵢₙ. For counterflow ε = [1 − e^(−NTU(1−Cᵣ))]/[1 − Cᵣ e^(−NTU(1−Cᵣ))] (at Cᵣ = 1, ε = NTU/(1+NTU)); parallel flow ε = [1 − e^(−NTU(1+Cᵣ))]/(1+Cᵣ).

Duty Q = ε Cₗᵢₙ (Tₕ,ᵢₙ − T₊,ᵢₙ), then Tₕ,ₖₜₜ = Tₕ,ᵢₙ − Q/Cₕ and T₊,ₖₜₜ = T₊,ᵢₙ + Q/C₊.

Worked example

Hot oil 2 kg/s at cp 2.0 kJ/kgK in at 120 °C; cooling water 4 kg/s at cp 4.18 kJ/kgK in at 25 °C; U = 400 W/m²K, A = 20 m², counterflow. Cₕ = 4.0, C₊ = 16.72 kW/K; Cᵣ = 0.239; NTU = 8000/4000 = 2.0; ε = 0.823; Q = 0.823 × 4.0 × 95 = 312.7 kW. Oil out at 41.8 °C, water out at 43.7 °C.

Assumptions and limitations

  • Steady state, constant U and cp, no phase change.
  • Shell-and-tube 1-2 arrangement uses the standard one-shell-pass relation.
  • Fouling raises resistance; include it in U.