Inverter and Battery Sizing Calculator
Size a home or small-site inverter and battery bank: continuous and surge load, backup hours, battery voltage and usable depth of discharge.
Enter the average continuous load, the highest surge (motor starting) load, backup hours and the battery bank voltage.
How it works
The inverter must cover the larger of the surge load and the continuous load, with a 25% margin on the continuous rating:
Inverter VA = max(surge, 1.25 × continuous) / power factor (0.8 typical).
Battery energy = continuous W × backup hours / inverter efficiency, and the bank capacity is that divided by the battery voltage and the usable depth of discharge.
Worked example
Continuous 800 W, surge 2000 W, backup 4 h on a 48 V bank, efficiency 0.9, lead-acid at 50% DoD. Inverter VA = max(2000, 1000)/0.8 = 2500 VA. Energy = 800 × 4/0.9 = 3556 Wh; Ah = 3556/(48 × 0.5) = 148 Ah, so a 48 V 150 Ah bank.
Assumptions and limitations
- Constant average load over the backup period; cycle-heavy loads need an energy audit.
- Lithium banks can use 80-90% DoD; lead-acid 50%.
- Cable size, temperature derating and charge rate are separate checks.