Power Factor Correction Capacitor Bank Calculator
Capacitor kVAR needed to improve the power factor of a load from its existing value to a target, with the resulting kVA and line-current reduction.
Enter the real power, the measured power factor and the target power factor (both lagging, 0 to 1).
How it works
The reactive power to compensate is the difference between the present and target reactive loads:
Q₊ = P × (tan φ₁ − tan φ₂), where cos φ₁ is the existing and cos φ₂ the target power factor.
After correction the apparent power drops to P/pf₂, and the line current falls in the same ratio pf₁/pf₂.
Worked example
P = 500 kW, pf₁ = 0.75, target pf₂ = 0.95. tan φ₁ = 0.8819, tan φ₂ = 0.3287. Q₊ = 500 × 0.5532 = 276.6 kVAR; use a 300 kVAR bank. kVA falls from 666.7 to 526.3, a 21% current reduction.
Assumptions and limitations
- Steady sinusoidal load; with high harmonic content use detuned (reactor-equipped) banks.
- Round up to a standard bank size and check for overcorrection at light load.
- Leading power factor (overcorrection) can attract penalties too; do not size beyond the target.