Power Factor Correction Capacitor Bank Calculator


Capacitor kVAR needed to improve the power factor of a load from its existing value to a target, with the resulting kVA and line-current reduction.

Enter the real power, the measured power factor and the target power factor (both lagging, 0 to 1).

Enter your values:
Results:

How it works

The reactive power to compensate is the difference between the present and target reactive loads:

Q₊ = P × (tan φ₁ − tan φ₂), where cos φ₁ is the existing and cos φ₂ the target power factor.

After correction the apparent power drops to P/pf₂, and the line current falls in the same ratio pf₁/pf₂.

Worked example

P = 500 kW, pf₁ = 0.75, target pf₂ = 0.95. tan φ₁ = 0.8819, tan φ₂ = 0.3287. Q₊ = 500 × 0.5532 = 276.6 kVAR; use a 300 kVAR bank. kVA falls from 666.7 to 526.3, a 21% current reduction.

Assumptions and limitations

  • Steady sinusoidal load; with high harmonic content use detuned (reactor-equipped) banks.
  • Round up to a standard bank size and check for overcorrection at light load.
  • Leading power factor (overcorrection) can attract penalties too; do not size beyond the target.