Psychrometric Air Properties Calculator
Moist-air properties from dry-bulb temperature, relative humidity and barometric pressure: humidity ratio, dew point, enthalpy, specific volume and vapour pressure.
Enter dry-bulb temperature in °C, relative humidity and the local barometric pressure.
How it works
Saturation vapour pressure uses the Tetens form pₕₛ = 0.61078 · e^(17.2694 T/(T+237.3)) kPa, and the vapour pressure is pₕ = φ · pₕₛ. Then:
- Humidity ratio W = 0.62198 · pₕ/(p − pₕ)
- Enthalpy h = 1.006 T + W(2501 + 1.86 T) kJ per kg of dry air
- Specific volume v = 0.287042 (T+273.15)(1+1.6078 W)/p m³/kg dry air
- Dew point is the exact inverse of the same Tetens equation.
Worked example
T = 30 °C, RH = 50%, p = 101.325 kPa. pₕₛ = 4.243 kPa, pₕ = 2.122 kPa. W = 0.62198 × 2.122/(101.325 − 2.122) = 0.01330 kg/kg = 13.30 g/kg. h = 1.006 × 30 + 0.01330 × (2501+55.8) = 64.19 kJ/kg dry air. v = 0.8740 m³/kg. Dew point = 18.4 °C.
Assumptions and limitations
- Tetens vapour-pressure correlation; within about 0.06 kPa of ASHRAE values from 0 to 40 °C.
- Ideal-gas moist-air model; not valid near saturation at high pressure.
- Enter barometric pressure for the site altitude (101.325 kPa at sea level).