Pump System Curve Calculator


System head curve H = H_static + K Q². Enter the static head and one known duty point (design flow and its friction head) to get the head at any other flow, then overlay it on the pump curve.

Enter the static head, the design flow with its friction head, and the flow where you want the system head.

Enter your values:
Results:

How it works

A piping system with a fixed static lift has head H(Q) = Hₛ + K Q², because friction loss varies with the square of the flow. One measured or calculated point fixes K:

K = Hₛᵠ(Qₜ)/Qₜ² at the design point, then H(Q) = Hₛ + K Q².

Where this curve crosses the pump HQ curve is the operating point. Throttling a valve raises K and moves the crossing up the pump curve; a VFD moves the pump curve instead.

Worked example

Static head 12 m, design flow 40 m³/h with 8 m friction. K = 8/40² = 0.005 m/(m³/h)². At Q = 30 m³/h, H = 12 + 0.005 × 900 = 16.5 m. At 50 m³/h, H = 12 + 12.5 = 24.5 m.

Assumptions and limitations

  • Fully turbulent friction (Q² law); laminar sections bend the curve.
  • Static head is the true elevation plus any pressure-head difference between source and destination.
  • For gravity systems with no lift, Hₛ = 0.