Room Cooling Load Calculator
Steady-state cooling load estimate for one room: conduction through walls and roof, solar gain through glass, people, lighting, equipment and outside-air infiltration, summed into a total to size the unit.
Enter peak design values. Areas in m², ΔT between outside and inside design conditions.
How it works
Each gain is estimated at peak conditions and summed:
- Conduction: Q = U × A × ΔT for walls, roof and glass.
- Solar through glass: Q = A × SHGC × peak solar factor.
- People: n × (sensible + latent W per person).
- Lighting: W/m² × floor area; equipment as entered.
- Infiltration: Q = 1.2 kg/m³ × airflow × enthalpy difference between outside and inside air.
Worked example
Room 5 × 4 m (20 m²), wall 20 m² at U 2.0, roof 20 m² at U 0.8, ΔT 8 K, glass 4 m² with SHGC 0.7 and solar factor 400 W/m², 4 people (75 W sensible + 55 W latent each), lighting 10 W/m², equipment 300 W, infiltration 20 L/s with Δh 12 kJ/kg. Conduction = 2×20×8 + 0.8×20×8 + 5×4×8 = 608 W; solar = 4×0.7×400 = 1120 W; people = 520 W; lights 200 W; equipment 300 W; infiltration = 1.2×0.020×12000 = 288 W. Total ≈ 3.04 kW = 0.86 TR.
Assumptions and limitations
- Steady-state (CLTD and time lag ignored); a full design uses the CLTD/CLF or RTS method.
- Peak solar factor is a broad guide: about 400 W/m² for sunlit glass, 150-250 W/m² for shaded or diffused.
- Add a safety margin of 10-15% before selecting equipment.