Transformer Parallel Operation Load Sharing Calculator
Load sharing between two transformers in parallel. The unit with the lower per-unit impedance (on its own base) takes more of the load; check that neither is overloaded and find the maximum combined load.
Nameplate kVA and percent impedance for each transformer, plus the total load to share.
How it works
Transformers in parallel share load in proportion to rating divided by percent impedance:
S₁ = S × (S₁ᵠ/Z₁) / (S₁ᵠ/Z₁ + S₂ᵠ/Z₂), and similarly for S₂.
The maximum total load without overloading either unit is set by whichever reaches its rating first: Sₗₐₓ = minᵢ [ Zᵢ × (S₁ᵠ/Z₁ + S₂ᵠ/Z₂) ].
Worked example
T1: 1000 kVA, 5%; T2: 500 kVA, 4%; total load 1200 kVA. Shares: 1000/5 = 200 and 500/4 = 125, so T1 takes 1200 × 200/325 = 738 kVA (73.8%) and T2 takes 462 kVA (92.3%). Sₗₐₓ = min(5,4) × 325 = 1300 kVA: above that, T2 overloads first.
Assumptions and limitations
- Same voltage ratio, vector group and phase angle shift; paralleling unlike units causes circulating current.
- Impedances treated as equal in X/R angle; close enough for a loading check.
- Percent impedances on each transformer’s own kVA base, as on the nameplate.