Transformer Parallel Operation Load Sharing Calculator


Load sharing between two transformers in parallel. The unit with the lower per-unit impedance (on its own base) takes more of the load; check that neither is overloaded and find the maximum combined load.

Nameplate kVA and percent impedance for each transformer, plus the total load to share.

Enter your values:
Results:

How it works

Transformers in parallel share load in proportion to rating divided by percent impedance:

S₁ = S × (S₁ᵠ/Z₁) / (S₁ᵠ/Z₁ + S₂ᵠ/Z₂), and similarly for S₂.

The maximum total load without overloading either unit is set by whichever reaches its rating first: Sₗₐₓ = minᵢ [ Zᵢ × (S₁ᵠ/Z₁ + S₂ᵠ/Z₂) ].

Worked example

T1: 1000 kVA, 5%; T2: 500 kVA, 4%; total load 1200 kVA. Shares: 1000/5 = 200 and 500/4 = 125, so T1 takes 1200 × 200/325 = 738 kVA (73.8%) and T2 takes 462 kVA (92.3%). Sₗₐₓ = min(5,4) × 325 = 1300 kVA: above that, T2 overloads first.

Assumptions and limitations

  • Same voltage ratio, vector group and phase angle shift; paralleling unlike units causes circulating current.
  • Impedances treated as equal in X/R angle; close enough for a loading check.
  • Percent impedances on each transformer’s own kVA base, as on the nameplate.