Wire Size Calculator (Ampacity and Voltage Drop)
Check a copper wire size against your load: NEC ampacity limit and voltage drop over the circuit length, for single-phase and three-phase runs, in AWG.
Enter the load and run, then pick a gauge to check.
How it works
Ampacity uses the NEC limits most US residential cable must respect (14 AWG = 15 A, 12 = 20 A, 10 = 30 A, then the 75°C table for 8 AWG and up). Voltage drop = multiplier × current × 2-way length × wire resistance; the multiplier is 2 for single-phase and √3 for three-phase.
- Keep drop at or under 3% on branch circuits and 5% total for feeder plus branch (NEC informational note).
- If the drop check fails, go up one or two gauges and re-run the check.
- Values are for copper. Aluminium needs roughly two sizes larger and special terminations.
Guidance, not an electrical design. Final wire and breaker selection follows the NEC and local code; continuous loads need 125% sizing and a licensed electrician should confirm the work.