Solar PV String Sizing Calculator


Find how many modules you can put in series per string: the maximum from the inverter's absolute voltage limit with cold-corrected V(oc), the minimum from the MPPT window with hot-corrected V(mp), and the string count for your target array size.

Enter module and inverter datasheet values plus site temperature extremes.

Inserisci i valori:

Negative, from the datasheet (typical -0.25 to -0.35 %/°C).

Risultati:

How it works

Module voltage rises in the cold: V(oc,cold) = V(oc) × (1 + β·(T(min) − 25)/100). The string must satisfy V(oc,cold)×N ≤ inverter absolute maximum, and stay inside the MPPT window at both temperature extremes: N(min) from hot V(mp) against the MPPT floor, N(max) from STC V(mp) against the MPPT ceiling.

  • Any string size between the computed min and max (inclusive) is valid; larger strings use less wiring.
  • The β for V(oc) is applied to V(mp) as an approximation - use the V(mp) coefficient from the datasheet if given.
  • Cell temperature, not air temperature: modules run about 25-30°C above ambient in full sun.

Check against the inverter maker's string-sizing tool before ordering; local electrical codes (e.g. NEC 690.7) may impose their own correction factors.