Duct Sizing Calculator (Equal Friction)


Size a round duct two ways: by a chosen air velocity (quiet/low-pressure design) or by a target friction rate in Pa/m (the equal-friction method), using Darcy-Weisbach with a Blasius friction factor.

Air at 20°C, 1.2 kg/m³. Convert rectangular results with equal area as a first step.

By velocity

Insira os valores:

3-5 m/s comfort, 5-8 commercial, 8-12 industrial.

Resultados:

How it works

By velocity: D = √(4Q/πv). Equal friction: Darcy-Weisbach rearranged, D = (8f·ρ·Q²/(π²·F))1/5, with the Blasius friction factor f = 0.3164·Re−0.25 refined over two iterations (air ρ = 1.2 kg/m³, μ = 1.81e-5 Pa·s).

  • Comfort systems: 0.8-1.2 Pa/m and 3-6 m/s; industrial: up to 2 Pa/m and 12 m/s.
  • Round up to the next standard duct size; friction drops as D5, so one size up roughly halves it.
  • Rectangular equivalent (equal flow and friction): D(e) = 1.3(a·b)^0.625/(a+b)^0.25 - invert to pick a and b.

Main-run sizing. Fittings, dampers and static regain are separate; use a ductulator or ASHRAE duct-design database for final design.