Motor Starting Current Calculator


Estimate a motor's full load current and the starting (inrush) current for the common starting methods: direct-on-line, star-delta, autotransformer, soft starter and variable frequency drive.

Enter the motor rating and starting method.

Insira os valores:
Resultados:

How it works

Full load current FLC = P / (√3·V·pf·η) for three-phase (drop the √3 for single-phase). Starting current = FLC × method multiplier. An autotransformer starter draws tap² × the DOL current from the supply (the motor sees tap ×).

  • DOL locked-rotor current is typically 6-7 x FLC; star-delta cuts both current and torque to one third.
  • Autotransformer 80/65/50% taps give 64/42/25% of DOL current and torque.
  • A VFD limits current to about 1.5 x FLC and is gentlest on the supply.

Estimate. Actual inrush depends on motor design (NEMA/IEC code letter); use the nameplate locked-rotor current for protection settings. For torque at start: T = 9550·P(kW)/n(rpm) rated, times the method's torque ratio.