Cable Thermal Withstand (Short-Circuit) Calculator


Check a cable's adiabatic short-circuit withstand (I²t), find the minimum conductor size for a fault level and clearing time, or apply installation derating factors to a tabulated ampacity.

k-factors to IEC 60364-4-43: Cu/PVC 115, Cu/XLPE 143, Al/PVC 76, Al/XLPE 94.

Withstand of a cable

Ange dina värden:
Resultat:

How it works

Adiabatic heating during a fault: I = k·S / √t (rearranged, S = I√t/k), where k depends on conductor and insulation to IEC 60364-4-43. The protective device let-through I²t must not exceed (kS)². Derated ampacity is the tabulated value times the installation factors: I' = I(z)·C(a)·C(g)·C(i).

  • Valid for clearing times from about 0.1 s to 5 s; below that, non-adiabatic effects help slightly.
  • Take k from the standard for other insulations (e.g. 60°C rubber, mineral).
  • The device let-through comes from the breaker/fuse manufacturer's curves, not the prospective fault alone.

Screening per IEC 60364-4-43. Confirm with the project's protection co-ordination study and the cable maker's data.