发电机选型
Size a generator for a group of motors: enter up to 7 motors with their starting method, and get the starting, running and recommended generator kVA.
Enter each motor's horsepower and starting method (up to 7 motors), then calculate the generator size you need.
How it works
For each motor the running kVA factor is 1.5/1.4/1.3 per HP (below 50 HP / 50-100 HP / 100 HP and above). Starting kVA uses a multiplier of 7/6/5 times that factor (up to 30 HP / 30-100 HP / 100 HP+), halved for Star-Delta starting. The generator must cover the largest cumulative starting kVA (halved for 3-phase diversity) and the total running kVA; the recommendation adds a 16% margin to the larger of the two.
Example
Two Direct-On-Line motors, 10 HP and 20 HP, on 3-phase: starting ≈ 81 kVA, running ≈ 32 kVA, recommended ≈ 94 kVA.
Note
Multipliers are the site's original rule-of-thumb from /enggcalc/generator size.htm. Always confirm against the motor nameplate starting current and the generator maker's motor-starting data.