Every cable has resistance, so some voltage is lost along its length. If the drop is too large, lights dim, motors run hot and sensitive equipment misbehaves. This guide shows how to calculate voltage drop for single phase and three phase circuits, and how to find the smallest cable that keeps the drop within a limit.
Formulas
First find the resistance per metre of the conductor: R′ = ρ ÷ A.
- R′ is the resistance in Ω/m.
- ρ is the resistivity in Ω·mm2/m. For copper at 20°C, ρ ≈ 0.0172. For aluminium at 20°C, ρ ≈ 0.0282.
- A is the conductor cross-sectional area in mm2.
Single phase (or DC), two conductors: ΔV = 2 × L × I × R′
Three phase, balanced load (line to line drop): ΔV = √3 × L × I × R′
where L is the one-way cable length in metres and I is the load current in amps. The factor 2 appears because current flows out and back. In percent: ΔV% = ΔV ÷ V × 100.
Minimum conductor area for an allowed drop:
- Single phase: Amin = 2 × ρ × L × I ÷ ΔVmax
- Three phase: Amin = √3 × ρ × L × I ÷ ΔVmax
Assumptions
- The load is resistive or has a power factor close to 1. Cable reactance is ignored, which is reasonable for small cables but not for large ones.
- Conductor temperature is 20°C. A hot cable has higher resistance.
- The three phase load is balanced.
- Length is the one-way route length, not the total conductor length.
Worked example 1: single phase
Given: 230 V single phase supply, load current 20 A, one-way length 30 m, 4 mm2 copper cable.
Resistance: R′ = 0.0172 ÷ 4 = 0.0043 Ω/m.
Voltage drop: ΔV = 2 × 30 × 20 × 0.0043 = 5.16 V.
Percent: 5.16 ÷ 230 × 100 = 2.24 percent.
Finding the minimum size for a 3 percent limit
Allowed drop: 0.03 × 230 = 6.9 V. Then Amin = 2 × 0.0172 × 30 × 20 ÷ 6.9 = 2.99 mm2. The next standard size above that is 4 mm2, which gives 2.24 percent, as calculated. A 6 mm2 cable would give 1.50 percent.
Calculators that work in circular mils give the same area in those units: 2.99 mm2 is about 5900 circular mils, since 1 mm2 = 1973.5 circular mils.
Worked example 2: three phase
Given: 400 V three phase, 50 A, one-way length 80 m, 16 mm2 copper.
R′ = 0.0172 ÷ 16 = 0.001075 Ω/m. ΔV = 1.732 × 80 × 50 × 0.001075 = 7.45 V, which is 7.45 ÷ 400 × 100 = 1.86 percent.
Effect of temperature
Copper resistance rises about 0.393 percent per °C. At a conductor temperature of 70°C the resistivity is about 0.0172 × (1 + 0.00393 × 50) = 0.0206 Ω·mm2/m. The single phase example then gives 6.17 V, or 2.68 percent, instead of 2.24 percent. For a heavily loaded cable this is a real difference.
Typical limits
Many codes and design guides suggest keeping the drop to about 3 percent on a branch circuit and about 5 percent overall from supply to load, but the exact limits depend on the country, the installation standard and the type of load. Check the standard that applies to your project.
Limitations
This method ignores cable reactance, power factor effects, harmonics, motor starting current (which causes a much larger temporary drop), bunching and ambient temperature derating, and the cable's current carrying capacity. A cable that passes the voltage drop check must still be able to carry the current safely and be protected correctly. Use the voltage drop result together with ampacity and protection checks.
Try the calculators
- Voltage Drop Calculator for allowed drop, minimum conductor area and minimum wire size, single or three phase.
- Wire Size Calculator for checking wire sizes.
- Related reading: Ohm's Law explained with practical examples.