Types of Foundation and Their Applications


· CalculatorEdge Editorial Team

Every structure stands on a foundation, and the foundation's job is to move the loads from the building into the ground without failing the soil or settling too much. Foundations come in two families: shallow foundations, which spread the load near the surface, and deep foundations, which carry the load down to stronger soil or rock. This article explains the main types, when each is used, and how a first bearing capacity check works.

Shallow foundations

A shallow foundation is one whose depth is about the same as its width or less, typically within 3 m of the surface. It is the cheapest option when the soil near the surface is strong enough.

  • Strip footing: a continuous strip of concrete under a load-bearing wall. Common for houses and small buildings on firm soil.
  • Isolated or spread footing: a square or rectangular pad under a single column. Used for framed buildings where loads arrive at points.
  • Combined footing: one pad carrying two or more columns, used when columns are close together or near a boundary.
  • Raft or mat foundation: a single slab under the whole building. It spreads the load over the largest possible area and suits weak soil or heavy structures, and it helps when settlement must stay uniform.

Deep foundations

A deep foundation extends well below the surface to reach soil or rock that can carry the load. It is chosen when the upper soil is weak, the loads are heavy, or uplift and lateral forces matter.

  • Driven piles: precast concrete, steel or timber piles hammered or vibrated into the ground. Fast to install and the driving record gives a capacity estimate.
  • Bored piles (drilled shafts): holes drilled and filled with concrete, often reinforced. They handle very heavy loads and cause little vibration, which matters near existing buildings.
  • Caissons: large-diameter shafts or boxes sunk to a firm stratum, used for bridges and towers.
  • Micropiles: small-diameter drilled and grouted piles for restricted access or underpinning.

How to choose

Ground and loading conditionUsual choice
Firm soil near the surface, light to medium loadsStrip or spread footings
Weak upper soil over a large plan areaRaft foundation
Weak soil over stronger soil or rock at depthPiles to the firm stratum
Heavy point loads, bridges, towersBored piles or caissons
Soft clay where no firm layer is reachableFriction piles, designed on settlement
Expansive or fill soilPiles below the active zone, or soil improvement plus raft

The final choice weighs soil investigation results, loads, settlement limits, groundwater, cost and construction access. Two structures on the same street can need different foundations.

Key terms and units

  • qu: ultimate bearing capacity, the pressure that fails the soil, in kPa (kN/m²).
  • qa: allowable bearing pressure, the working pressure after a factor of safety, in kPa.
  • FoS: factor of safety, usually 2.5 to 3 for bearing capacity.
  • c: soil cohesion in kPa. φ: angle of internal friction in degrees. γ: unit weight of soil in kN/m³.
  • B: footing width in m. Df: depth of the footing base below ground in m.

Terzaghi's equation for a strip footing is qu = c·Nc + γ·Df·Nq + 0.5·γ·B·Nγ, where Nc, Nq and Nγ are bearing capacity factors that depend only on φ.

Assumptions

  • The soil is homogeneous and its properties (c, φ, γ) come from a proper site investigation.
  • The load is vertical and centred; no moment or lateral load.
  • The groundwater table is deep enough not to reduce the effective unit weight.
  • Terzaghi's factors apply to general shear failure in a strip footing; shape and depth corrections for other footing shapes are separate.

Worked example: bearing capacity of a strip footing

Given: a strip footing of width B = 1.5 m with its base Df = 1.2 m below ground. The soil has c = 12 kPa, φ = 28° and γ = 18 kN/m³. For φ = 28°, the Terzaghi factors are Nc = 31.61, Nq = 17.81 and Nγ = 13.70.

Step 1, the three terms: cohesion term c·Nc = 12 × 31.61 = 379.3 kPa. Overburden term γ·Df·Nq = 18 × 1.2 × 17.81 = 384.7 kPa. Width term 0.5·γ·B·Nγ = 0.5 × 18 × 1.5 × 13.70 = 184.9 kPa.

Step 2, ultimate capacity: qu = 379.3 + 384.7 + 184.9 = 949.0 kPa.

Step 3, net and allowable: subtract the overburden pressure γ·Df = 21.6 kPa to get the net ultimate capacity, 927.4 kPa. With a factor of safety of 3, the allowable net pressure qa = 927.4 ÷ 3 = 309.1 kPa.

Step 4, what it means: the footing can carry about 309.1 kPa × 1.5 m = 464 kN per metre run of wall, subject to a separate settlement check.

Limitations

Bearing capacity is only half of the design. Settlement, both total and differential, often controls the choice, especially on clay. Terzaghi's equation is a simplification: real designs apply shape, depth and inclination factors, account for groundwater, layered soil and local shear, and follow the current code. Deep foundations add side friction and end bearing, pile group effects and negative skin friction. Every real foundation design needs a site investigation and a qualified geotechnical engineer. Treat this article as an introduction, not a design method.