Understanding Three-Phase Electrical Power


· CalculatorEdge Editorial Team

Three-phase power is the standard way to deliver electricity to factories, large buildings and motors. It uses three alternating voltages that are shifted by 120 degrees, so the total power delivered is smooth and the wiring is efficient. This article explains the key relations and works through a motor example.

Why three phase?

  • It delivers constant power to the load, which makes motors run smoothly.
  • For the same power it needs less conductor material than single phase.
  • Three-phase induction motors are simple, rugged and start without extra circuits.

Line and phase values

ConnectionVoltageCurrent
Star (wye)VL = √3 × VphIL = Iph
DeltaVL = VphIL = √3 × Iph

VL and IL are the line (line to line) voltage and line current. Vph and Iph are across and through each load winding.

Power formulas

  • Real (active) power: P = √3 × VL × IL × cosφ (W)
  • Apparent power: S = √3 × VL × IL (VA)
  • Reactive power: Q = √3 × VL × IL × sinφ (var)
  • Power factor: cosφ = P ÷ S
  • Line current from power: IL = P ÷ (√3 × VL × cosφ)

These hold for a balanced load, whether it is connected in star or delta, when VL and IL are line values.

Assumptions

  • The three phases are balanced: equal voltage magnitudes, equal currents and equal power factor on each phase.
  • The waveforms are sinusoidal. Strong harmonics change the real relations.
  • Voltage is line to line and current is the line current.

Worked example: a three-phase motor

Given: a motor on a 400 V three-phase supply draws 25 A at a power factor of 0.85. Its efficiency is 90 percent.

Apparent power: S = 1.732 × 400 × 25 = 17 321 VA = 17.32 kVA.

Real power drawn: P = 17 321 × 0.85 = 14 722 W = 14.72 kW.

Reactive power: sinφ = √(1 − 0.852) = 0.5268, so Q = 17 321 × 0.5268 = 9 124 var = 9.12 kvar.

Shaft output: 14.72 kW × 0.90 = 13.25 kW. In horsepower that is 13 250 ÷ 746 = 17.8 hp (mechanical hp).

Check: P2 + Q2 = 14.722 + 9.122 = 216.7 + 83.2 = 299.9, and S2 = 17.322 = 300.0, so the power triangle closes.

Finding the current for a given load

A 15 kW load at 400 V and power factor 0.8: IL = 15 000 ÷ (1.732 × 400 × 0.8) = 27.06 A. The same 15 kW on a single phase 230 V supply at power factor 0.8 would need 15 000 ÷ (230 × 0.8) = 81.5 A, about three times the current. This is why three phase is used for large loads.

Star and delta example

On a 400 V supply, each winding of a star-connected load sees Vph = 400 ÷ 1.732 = 230.9 V. In a delta connection, a line current of 25 A splits into a winding current of 25 ÷ 1.732 = 14.43 A.

Limitations

These formulas apply to balanced, sinusoidal loads. Unbalanced loads, heavy harmonics from variable speed drives, and neutral currents need more detailed analysis. The motor example uses the stated efficiency and power factor, which change with load, so use the nameplate and the maker's curves for design. Never size protection or cables from these relations alone: use the relevant electrical code.