Heating Load (Building Envelope) Calculator
Steady-state heat loss of a room or building: transmission through each envelope element (U x A x ΔT) plus infiltration from air changes, with a design margin for heater sizing.
Enter each element with its U-value. Skip unused elements by leaving area empty.
How it works
Transmission loss per element: Q = U × A × ΔT. Infiltration: Q = 0.33 × ACH × V × ΔT (W), using the heat capacity of air (0.33 W per m³/h per K). Total = sum of elements + infiltration; design load adds your margin.
- U-values: uninsulated brick wall ~2.0, insulated cavity ~0.3-0.5, single glazing ~5.8, double ~2.8, triple ~1.6 W/m²K.
- Infiltration: 0.2-0.5 ACH for tight modern buildings, 1-2 for leaky older ones.
- Steady-state: thermal mass and solar/internal gains are not credited, which is conservative for sizing.
Screening estimate (degree-hour steady state). Full room-by-room load calculations follow CIBSE / ASHRAE methods with orientation, ventilation and intermittent-heating allowances.