How to Select the Correct Cable Size


· CalculatorEdge Editorial Team

The correct cable size is the smallest conductor that carries the load current without overheating, keeps the voltage drop within limits, and survives a fault until the protective device trips. This article shows the first two checks with a worked example. The third check, short-circuit withstand, is covered briefly at the end.

The three checks

  1. Current carrying capacity (ampacity). The cable must carry the design current at the installed conditions without exceeding its temperature rating.
  2. Voltage drop. The drop along the cable must stay within the limit for the circuit, so the load gets enough voltage.
  3. Short-circuit withstand. The conductor must handle the fault current for the time the protective device takes to clear it.

The final size is the largest result of these checks.

Formulas and units

  • Design current: Ib in A. For a motor or load, use the full load current. For a feeder, use the sum of connected loads after diversity.
  • Required tabulated rating: It = Ib ÷ (Ca × Cg), where Ca is the ambient temperature factor and Cg is the grouping factor. Both are dimensionless and below 1 for hot or crowded installations.
  • Single-phase voltage drop: ΔV = 2 × I × L × ρ ÷ A, with I in A, L the one-way length in m, ρ the resistivity in Ω·mm²/m and A the conductor area in mm².
  • Three-phase voltage drop: ΔV = √3 × I × L × ρ ÷ A (line to line, resistance only).
  • Percentage drop: ΔV% = ΔV ÷ V × 100.

Assumptions

  • Copper conductors. ρ = 0.0225 Ω·mm²/m is used as a conservative value for a conductor near its 70 °C operating temperature (about 0.0172 at 20 °C).
  • Resistive drop only. Reactance matters for large conductors and is ignored here.
  • Drop limit of 3 percent for a branch circuit, a common design target. Your code or client may set a different limit.
  • The ampacity table, the correction factors and the installation method come from the code you design to. The factors below are example values.

Worked example: a 32 A single-phase circuit

Given: a 230 V single-phase load drawing 32 A, run 40 m one way in a conduit with other circuits. Ambient factor Ca = 0.94 and grouping factor Cg = 0.80.

Step 1, ampacity. It = 32 ÷ (0.94 × 0.80) = 42.55 A. Pick a size whose tabulated rating for your installation method is at least 42.6 A. Suppose that gives 6 mm² as the smallest size.

Step 2, voltage drop for 6 mm². ΔV = 2 × 32 × 40 × 0.0225 ÷ 6 = 9.60 V. As a percentage: 9.60 ÷ 230 = 4.17 percent. This is above the 3 percent limit, so 6 mm² fails.

Step 3, try 10 mm². ΔV = 2 × 32 × 40 × 0.0225 ÷ 10 = 5.76 V, which is 2.50 percent. This passes. The selected size is 10 mm².

The lesson: on long runs voltage drop, not ampacity, often decides the size. Doubling the length or the current doubles the drop, and doubling the area halves it.

Short-circuit withstand

A common check uses the adiabatic equation: A ≥ Isc × √t ÷ k, with Isc in A, t in seconds and A in mm². The constant k depends on the conductor and insulation material and is given in the code.

Limitations

This is a simplified method for sizing studies. It ignores reactance, harmonics, cable temperature rise from the load itself, soil thermal resistivity for buried cables, and the starting current of motors. Ampacity tables differ between standards such as IEC, NEC and BS 7671, so always take the final rating, correction factors and drop limit from the standard that applies and have a qualified person check the design.