11 reviewed questions. Choose answers, then Calculate. Clear resets all selections. Unanswered questions score zero and remain in the percentage denominator. Open the answer review below for sources.
Answers and sources
Reviewed 17 November 2026. Ambiguous, malformed and unverified legacy questions have been removed. Wording and answer choices have been corrected where needed. This is a study quiz, not certification of engineering or laboratory decisions.
Question 1: answer and source
In the working stress method, the depth of the critical (balanced) neutral axis of a singly reinforced beam is _____ (m = modular ratio, r = ratio of permissible stress in steel to permissible stress in concrete, d = effective depth)
Answer: (m x d) / (m + r)
WSM balanced section: x_c = k.d with k = m.sigma_cbc/(m.sigma_cbc + sigma_st) = m/(m+r) when r = sigma_st/sigma_cbc, so x_c = (m.d)/(m+r). Stem clarified to define m, r and d; key unchanged.
Question 2: answer and source
As per IS 456, the minimum horizontal spacing between parallel main reinforcement bars of the same size should not be less than _____ diameters (or 5 mm more than the nominal maximum size of coarse aggregate, if greater)
Answer: 1
IS 456:2000 cl 26.3.1(a): minimum horizontal distance between parallel main bars = bar diameter (equal sizes), or 5 mm more than the nominal maximum aggregate size if greater. Legacy key '2 diameters' wrong; correct is 1. Stem reworded to state the aggregate-size condition.
Question 3: answer and source
Rapid hardening cement is actually early _____ cement
Answer: strength
Rapid-hardening cement sets in about the same time as OPC but develops high EARLY STRENGTH ('High Early Strength Cement'). Legacy key 'setting' wrong.
Question 4: answer and source
Ductility of steel decreases with a percentage _____ of carbon steel
Answer: increase
Increasing carbon content raises strength but lowers ductility of steel.
Question 5: answer and source
_____ ratio of steel, within elastic limit, varies from 0.25 to 0.33
Answer: Poisson's
Poisson's ratio of structural steel is about 0.3 (commonly quoted range 0.25-0.33 within the elastic limit).
Question 6: answer and source
The process of adding extra carbon to the surface of steel is known as _____
Answer: Carburising
Diffusing carbon into the surface of low-carbon steel is carburising (case hardening). Legacy key 'Carbon treatement' wrong and non-standard.
Question 7: answer and source
Maximum shear force occurs at the edge of a base plate in a _____ footing
Answer: Grillage
In a grillage footing 'the maximum shear force develops at the edge of the base plate'. Legacy key 'Rectangular' wrong; correct is Grillage.
Question 8: answer and source
As per IS : 456 in a two-way slab, the width of the middle strip along each span should be
Answer: 3/4 of width of the span in that direction
Two-way slab design: middle strips three-quarters of the panel width carry the Annex D moments, edge strips one-eighth each.
Question 9: answer and source
The reinforcement provided in the form of ties or stirrups or binders in a column is known as
Answer: transverse reinforcement
IS 456:2000 cl 26.5.3: ties/helical binding in a column are the column's transverse reinforcement.
Question 10: answer and source
Load carrying capacity of long columns are less as compared to short columns due to
Answer: buckling effect of columns
Long (slender) columns lose capacity through buckling - Euler's critical load falls with slenderness.
Question 11: answer and source
As per IS : 456 the thickness of footing edge on soils should not be less than
Answer: 15 cm
IS 456:2000 cl 34.1.2: thickness at the edge of a footing on soil shall not be less than 150 mm (15 cm).
Change log: 17 November 2026
Original question numbers and review decisions
- Original Q1: corrected. WSM balanced section: x_c = k.d with k = m.sigma_cbc/(m.sigma_cbc + sigma_st) = m/(m+r) when r = sigma_st/sigma_cbc, so x_c = (m.d)/(m+r). Stem clarified to define m, r and d; key unchanged.
- Original Q2: corrected. IS 456:2000 cl 26.3.1(a): minimum horizontal distance between parallel main bars = bar diameter (equal sizes), or 5 mm more than the nominal maximum aggregate size if greater. Legacy key '2 diameters' wrong; correct is 1. Stem reworded to state the aggregate-size condition.
- Original Q3: dropped. The cited code also limits loading class to 3 kN/m2; that condition is absent. Drop rather than silently add it.
- Original Q4: dropped. A ribbed slab does not necessarily provide a plain ceiling or all listed insulation benefits; one MCQ page does not establish the broad claim.
- Original Q5: dropped. Rule of thumb ('max BM when water depth = half the short wall') could not be confirmed against any reputable design source after targeted searches; excluded per verification-only policy.
- Original Q6: corrected. Rapid-hardening cement sets in about the same time as OPC but develops high EARLY STRENGTH ('High Early Strength Cement'). Legacy key 'setting' wrong.
- Original Q7: dropped. The cited stair-design source could not be read (403); the numerical rule is not established by inspected evidence.
- Original Q8: verified. Increasing carbon content raises strength but lowers ductility of steel.
- Original Q9: verified. Poisson's ratio of structural steel is about 0.3 (commonly quoted range 0.25-0.33 within the elastic limit).
- Original Q10: dropped. Slenderness uses effective length, but only unsupported length is stated and end restraint is absent.
- Original Q11: corrected. Diffusing carbon into the surface of low-carbon steel is carburising (case hardening). Legacy key 'Carbon treatement' wrong and non-standard.
- Original Q12: dropped. The generic metal-hardening claim is broader than the steel carburising source supports.
- Original Q13: corrected. In a grillage footing 'the maximum shear force develops at the edge of the base plate'. Legacy key 'Rectangular' wrong; correct is Grillage.
- Original Q14: dropped. IS 800 Table 3 applies the 350 limit to a particular truss/bracing tie not effective under compression, not every reversal case in the stem.
- Original Q15: dropped. Stem says 0.67L but IS 800:1984 Table 5.2 / IS 800:2007 Table 11 give 0.65L for a member held in position and restrained in direction at both ends. The only fix would be editing the stem so the keyed option fits - a guessed corruption, so dropped per revision rule.
- Original Q16: dropped. The theoretical Euler L/2 answer is not distinguished from code-design effective length.
- Original Q17: dropped. Mangled worked example: the source problem is ISA 125x75x10 with 27 mm rivets (this bank says 155x75x10), and the claimed 27 t strength is not reproducible (working-stress calculation gives ~22 t). Data internally inconsistent.
- Original Q18: dropped. No code deflection limit applies to pure tension members (ties); IS 800 deflection limits cover flexural members (beams, girders, purlins). Key 'L/350' unverifiable.
- Original Q19: dropped. The cited page resolves to a website-unavailable message; no inspected source supports the retained row.
- Original Q20: dropped. A single MCQ page is insufficient support for a universal preliminary beam-width rule.
- Original Q21: dropped. Continuous-beam support moment does not by itself require a doubly reinforced section.
- Original Q22: dropped. Excluded from release because available support was insufficient.
- Original Q23: verified. Two-way slab design: middle strips three-quarters of the panel width carry the Annex D moments, edge strips one-eighth each.
- Original Q24: verified. IS 456:2000 cl 26.5.3: ties/helical binding in a column are the column's transverse reinforcement.
- Original Q25: verified. Long (slender) columns lose capacity through buckling - Euler's critical load falls with slenderness.
- Original Q26: verified. IS 456:2000 cl 34.1.2: thickness at the edge of a footing on soil shall not be less than 150 mm (15 cm).
- Original Q27: dropped. Keyed M200 reflects withdrawn pre-2000 practice; current IS 2911 (Part 1/Sec 1):2010 requires minimum grade M25 for cast-in-situ piles, and M250 is not among the options.
- Original Q28: dropped. The relation needs constant EI and a sign convention, neither stated.
- Original Q29: dropped. Extreme free fibres and free edges overlap as answer choices; the linked source was also inaccessible.
- Original Q30: dropped. Keyed M15 conflicts with IS 3370 minimum grades for liquid-retaining structures (M20 in the 1965 edition, M30 in the 2021 edition); no edition supports M15.
- Original Q31: dropped. The exact upper-limit wording conflicts with the cited approximately 2.14 percent boundary.