Series and Parallel Pump Operation Calculator
See how two identical pumps behave in series and in parallel against your system curve, compared with a single pump. Pump curves are modelled as H = H(0) − kQ² and the system as H = H(static) + KQ².
Enter the pump curve (shutoff head + rated point) and the system curve.
How it works
Each pump is modelled as H = H(0) − kQ² with k fitted through your rated point. The system curve is H = H(static) + KQ². In series the heads add at the same flow (H(0) and k double); in parallel the flows add at the same head. The operating point is where the combined curve crosses the system curve.
- Series gains are largest on steep (friction-dominated) systems; parallel gains are largest on flat (static-dominated) systems. Check the gain figures above.
- Neither arrangement doubles the flow: the system curve decides.
- Verify each pump still runs near its best efficiency point and within NPSH limits.
Simplified parabolic model. Use the manufacturer's real curves for selection; dissimilar pumps need composite-curve construction.